PV Disconnect
Installation
Dry Well Probe Sensor

The disconnect switch satisfies National Electrical Code requirements for a safety disconnect between the solar array and the controller. During installation and maintenance, switch off the disconnect switch to prevent shock and arc burn hazard.

Note:

Overload protection (fuses or circuit breaker) is NOT required in the solar array circuit.

Explanation:
  1. Short circuit current from the solar array can never reach the ampacity (maximum safe amps capacity) of the recommended wire.
  2. The PS- controller has internal overload protection.
Caution:

Loose connections are a comon cause offailure. Pull each connection to confirm.

Caution:

If you are not using a low-water probe, connect a small wire between terminals 1 and 2.